Type |
Canopied |
|
Standby power LTP |
275 kVA |
|
Standby power LTP |
220 kW |
|
Rated prime power (PRP) |
254 kVA |
|
Rated prime power (PRP) |
203 kW |
|
Rated continuous power (COP) |
254 kVA |
|
Rated continuous power (COP) |
203 kW |
|
Phases |
3 |
|
Voltage |
400 V |
|
Frequency |
50 Hz |
|
Battery charger current |
60 A |
|
Circuit breaker |
400 |
|
Ratio |
0,99 |
|
|
Engine manufacturer |
Volvo |
|
Model |
TAD740GE |
|
Stroke |
4, diesel |
|
Fuel |
Diesel |
|
Number of cylinders and disposition |
6, inline |
|
Displacement |
7280 cm³ |
|
Air intake |
Turbocharged, intercooled |
|
Starting system |
Electric |
|
Nominal operating speed |
1500 rpm |
|
Speed governor |
Electronic |
|
SAE |
n.a. |
|
Flywheel |
n.a. |
|
Continuous power COP |
220 kW |
|
Prime power PRP |
220 kW |
|
Standby power LTP |
242 kW |
|
Lube oil capacity |
29 l |
|
Coolant capacity |
36,9 l |
|
Fuel consumption at 100% PRP |
52 l/h |
|
Fuel consumption at 75% PRP |
39 l/h |
|
Maximum lube oil consumption at PRP |
0,04 % |
|
Electric circuit voltage |
24 V |
|
Engine derating |
1,0 |
|
Cooling fan |
Mechanical |
|
|
Alternator
specifications
( alternator
utilised can vary, please ask for model at time of
order) |
|
Alternator manufacturer |
Stamford |
|
Model |
UCDI 274K |
|
Poles |
4 |
|
Revolution speed |
1500 rpm |
|
Voltage |
400 V |
|
Frequency |
50 Hz |
|
Continuous nominal power at 40°C - COP |
250 kVA |
|
Continuous nominal power at 27°C - PRP |
265 kVA |
|
Standby power at 27 °C - LTP |
275 kVA |
|
Continuous active power at 27°C - PRP |
212 kW |
|
Efficiency at 75% load |
92,7 % |
|
Efficiency at 100% load |
92,4 % |
|
Maximum admitted overload |
10% for 1 hour every 12 hours of running time S2 |
|
Voltage regulation system |
Electronic |
|
Alternator derating |
1,0 |
|
Protection grade |
IP 23 |
|
|
Fuel tank location |
Internal |
|
Fuel tank capacity |
330 l |
|
Running time at 100% PRP |
6,36 h |
|
Running time at 75% PRP |
8 h |
|
Measured acoustic power (LWA) at 10 mt |
97 dBA |
|
Noise level at 7 m |
72 dBA |
|
Guaranteed noise level (LWA) |
97 dBA |
|
|
Length |
3500 mm |
|
Width |
1300 mm |
|
Height |
2150 mm |
|
Dry weight |
2823 kg |
|
|
Cooling fan air flow rate |
191,8 m³/min |
|
Combustion air flow at PRP |
14,7 m³/min |
|
Exhaust gas flow at PRP |
39,2 m³/min |
|
Exhaust gas temperature at LTP |
525 °C |
|
Exhaust pipe diameter |
n.a. |
|
Maximum admitted total exhaust backpressure |
100 mbar |
|
|
Mechanical speed governor |
Optional |
|
Electronic speed governor |
Optional |
|
Radio interference suppression |
Optional |
|
Standard AVR (Automatic Voltage Regulator) |
Optional |
|
Optional AVR (Automatic Voltage Regulator) |
Optional |
|
Underspeed protection |
Optional |
|
12 V electric circuit |
Optional |
|
24 V electric circuit |
Optional |
|
Air intake filter |
Optional |
|
|
On-board ACP (Automatic Control Panel) |
Optional |
|
ACP (Automatic Control Panel), delivered loose |
Optional |
|
On-board LTS (Load Transfer Switch) panel |
Optional |
|
LTS (Load Transfer Switch) panel, delivered
loose |
Optional |
|
Power section with circuit breaker delivered
loose |
Optional |
|
Power section with on-board circuit breaker |
Optional |
|
Differential protection |
Optional |
|
Engine coolant preheater |
Optional |
|
Manual oil draining pump |
Optional |
|
| Equipment:
basic engine configuration |
|
Optimized fuel consumption |
Optional |
|
| Equipment:
starting system |
|
Single pneumatic starter motor |
Optional |
|
Electric starter and compressed air starter |
Optional |
|
2 electric starters with separate power supply |
Optional |
|
|
Batteries |
Optional |
|
Battery liquid |
Optional |
|
Battery disconnecting device |
Optional |
|
| Equipment:
fuel feeding system |
|
Air filters with contamination indicator |
Optional |
|
Fuel level sensor (minimum and maximum) |
Optional |
|
Fuel main filter |
Optional |
|
Fuel prefilter water separator |
Optional |
|
Electric valve for fuel circuit |
Optional |
|
| Equipment:
lube oil system |
|
Lube oil filler neck, dipstick |
Optional |
|
Lube oil fine filter |
Optional |
|
Lube oil cooler |
Optional |
|
|
No silencer option |
Optional |
|
Catalytic silencer |
Optional |
|
Spark arrester |
Optional |
|
Flexible exhaust compensator |
Optional |
|
Connection flanges to exhaust line |
Optional |
|
|
Industrial silencer -15 dB(A) |
Optional |
|
Residencial silencer -35 dB(A) |
Optional |
|
| Equipment:
engine switches and senders |
|
Fuel minimum level switch |
Optional |
|
Coolant minimum level switch |
Optional |
|
Coolant temperature switch |
Optional |
|
Coolant temperature sender |
Optional |
|
Lube oil minimum level switch |
Optional |
|
Lube oil minimum pressure switch |
Optional |
|
Lube oil maximum temperature switch |
Optional |
|
Lube oil temperature sender |
Optional |
|
Lube oil pressure sender |
Optional |
|
|
Integrated fuel tank capacity 50 L |
Optional |
|
Integrated fuel tank capacity 120 L |
Optional |
|
Integrated fuel tank capacity 350 L |
Optional |
|
Integrated fuel tank capacity 800 L |
Optional |
|
Leak proof tray sized for integrated fuel tank
capacity |
Optional |
|
|
1.000 L underground storage fuel tank with
double wall |
Optional |
|
2.000 L underground storage fuel tank with
double wall |
Optional |
|
3.000 L underground storage fuel tank with
double wall |
Optional |
|
5.000 L underground storage fuel tank with
double wall |
Optional |
|
10.000 L underground storage fuel tank with
double wall |
Optional |
|
15.000 L underground storage fuel tank with
double wall |
Optional |
|
|
1.000 L outdoor storage fuel tank with single
wall and leak proof tray |
Optional |
|
2.000 L outdoor storage fuel tank with single
wall and leak proof tray |
Optional |
|
3.000 L outdoor storage fuel tank with single
wall and leak proof tray |
Optional |
|
5.000 L outdoor storage fuel tank with single
wall and leak proof tray |
Optional |
|
10.000 L outdoor storage fuel tank with single
wall and leak proof tray |
Optional |
|
15.000 L outdoor storage fuel tank with single
wall and leak proof tray |
Optional |
|
Automatic refilling system |
Optional |
|
|
1.000 L outdoor storage fuel tank with double
wall |
Optional |
|
2.000 L outdoor storage fuel tank with double
wall |
Optional |
|
3.000 L outdoor storage fuel tank with double
wall |
Optional |
|
5.000 L outdoor storage fuel tank with double
wall |
Optional |
|
10.000 L outdoor storage fuel tank with double
wall |
Optional |
|
15.000 L outdoor storage fuel tank with double
wall |
Optional |
|
|
Heating parts guard |
Optional |
|
Moving parts guard |
Optional |
|
|
Alternator assembled by flexible joint |
Optional |
|
Anti-vibration mountings |
Optional |
|
Flexible coupling disc |
Optional |
|
Screwed steel frame |
Optional |
|
Welded steel frame |
Optional |
|
|
Self-excited |
Optional |
|
Separately-excited by P.M.G. |
Optional |
|
Anti-condensation heater |
Optional |
|
Tropicalization treatment |
Optional |
|
Winding leads |
Optional |
|
1-phase sensing input |
Optional |
|
2-phase sensing input |
Optional |
|
3-phase sensing input |
Optional |
|
|
CT for parallel running with other gensets |
Optional |
|
cosPhi regulator |
Optional |
|